MX-1 SNIB3 Factory Default
Introduction
Velocity relies on the configuration of the IP address of the SNIB3. If the computer searching for the SNIB3 is on a different network than what the SNIB3 is programmed with, then resetting the SNIB3 to factory defaults may be necessary.
Solution:
Reset MX-1 SNIB3 to Factory Defaults
Power down the MX-1
Set configuration switches 1 through 4 to the ON position. Set Address to 0
Power on the SNIB3
a) Let it finish booting up, then power down again
b) Set switches 2-3 back to OFF. Set Address to 1
c) Power up the SNIB3
Use SNIBConfigurationTool or Velocity to assign IP4 Address
Detailed solution:
Reset MX-1 SNIB3 to Factory Defaults
Step 1
Disconnect all power from the MX-1 Controller, If only powered by POE then you will only need to disconnect the RJ45 Network Cable (Ethernet PoE+). Set Address to 0.
Step 2
Set configuration switches 1-4 to the ON position (down). Set Address dial to 0.
Step 3
Reconnect the PoE+ RJ45 cable, wait approximately 1 minute for Controller to boot up.
Disconnect the PoE+ RJ45 cable and Set Switches 2 and 3 off, Switch 1 and 4 on. Set Address to 1.
Step 4
Reconnect the PoE+ RJ45 cable, wait approximately 1 minute for Controller to boot up.
Launch the SNIB Configuration Tool, located on the Velocity Server. C:\Program Files (x86)\Identiv\Velocity\Tools\SNIBConfigTool\SNIBConfigTool.exe
SNIB Hunt and Configure > Click Search > Locate and double click the Devices based on MAC address:
Uncheck Enable DHCP Mode.
Then Enter Device_Hostname, Device_IP_Address, Device_Subnet_Mask, and Device_Default_Gateway. This information may be supplied by the Network Administrator.
Choose “Send To Device” Choose YES on Popup notification and then Close SNIB Hunt and Configure Window.