80X0 uTrust Touch Secure Mullion Reader
Introduction
This document details the Physical Access Control Reader TouchSecure® and its basic operational and installation procedures. It covers the details of the Mullion form-factor reader.
Model: Connectivity/Standard MUL.
The reader comes in two variants for interfacing with the control panel:
Pigtail - 8000ABP, 8010ABP
Phoenix connectors - 8000ABT, 8010ABT, 8030ABC
P - refers to Pigtail, T - refers to Terminal (Phoenix header)
The reader comes in three variants in functionality
Standard HF Only - 8000ABP, 8000ABT
Standard HF LF - 8010ABP, 8010ABT
Connectivity HF LF - 8030ABC
P - refers to Pigtail, T - refers to Terminal (Phoenix header), C - refers to connectivity
In connectivity, Only Terminal version is available
Reader
Functionality
TouchSecure reader is a physical access control smart card reader that can read HF and LF contactless credentials, conforming to the following standards: ISO 14443 A & B, ISO15693. The reader can interface with an access control system equipped with a Wiegand or RS-485 serial interface.
Reader parts
The reader consists of the following main parts:
a. Top Casing
b. Touch Screen Reader with Bottom Casing
Reader variants
Product Details
Model Name | Connectivity/Standard MULLION. |
Device Type | RFID reader, 13.56MHz (HF) / 125 KHz (LF). |
Type of equipment | Potted reader. |
Interface Type | Pigtail Cable (11 Core + Drain) or Phoenix connectors and RJ45. |
Voltage Rating (8030ABC) | 6-16VDC or 48VDC on RJ45 Connector. |
Voltage Rating (All other models) | 5-16VDC. |
Communication protocol | Wiegand, RS-485 (2wire - Half Duplex), 10BaseT ETH. |
* Communication via Wiegand and OSDP was evaluated by UL and serves as the interface between the reader and panel, Communication via Ethernet was not evaluated by UL. |
Reader Specifications
Model | Operating Voltage | Current rating | Operating temp |
---|---|---|---|
8000ABP | 5 - 16VDC | Refer graph in section |
-35 to +65 Deg C |
8010ABP | 5 - 16VDC | Refer graph in section “Rated current at different operating voltages” | |
8030ABC | 6 - 16VDC |
Refer graph in section “Rated current at different operating voltages” |
0 to +49 Deg C |
PoE @ 48VDC |
*PoE sourcing equipment shall be UL 294 or UL 294B Listed with Class 2 output.
When the readers use PoE as a power source, the power input wiring from the control unit (i.e. Red and Black for 8030) shall be disconnected.
The maximum length of the Ethernet cable when using PoE as the power source in UL installations is limited to 30 meters (98.5 feet).
Standby Power is not provided by the Card Readers. The Standby Power Level is dependent on the external power source connected to the Card Reader.
All wiring or cables to the Card Readers shall be the shielded type.
Only UL Listed PoE sourcing equipment, or UL Listed power-limited power supply, or power-limited output from UL Listed control panel shall be used for the Power Over Ethernet feature. Cat 5e cabling is the minimum performance category recommended. These Card Readers when using PoE feature are not intended for outside wiring as covered by Article 800 of the US National Electrical Code, NFPA 70.
Rated current at different operating voltages
Rated current for Model 8000
Voltage (V) | Average Current (mA) | Peak Current (mA) |
---|---|---|
5V | 150 mA | 187 mA |
8V | 159 mA | 208 mA |
10V | 122 mA | 164 mA |
12V | 100 mA | 133 mA |
14V | 87 mA | 118 mA |
16V | 77 mA | 103 mA |
Rated current for Model 8010
Voltage (V) | Average Current (mA) | Peak Current (mA) |
---|---|---|
5V | 150 mA | 187 mA |
8V | 159 mA | 208 mA |
10V | 122 mA | 164 mA |
12V | 100 mA | 133 mA |
14V | 87 mA | 118 mA |
16V | 77 mA | 103 mA |
Rated current for Model 8030
Rated current for 6-16v Input
Voltage (V) | Average Current (mA) | Peak Current (mA) |
---|---|---|
6V | 273 mA | 308 mA |
8V | 251 mA | 292 mA |
10V | 219 mA | 273 mA |
12V | 167 mA | 211 mA |
14V | 144 mA | 178 mA |
16V | 128 mA | 158 mA |
Rated current for POE
Voltage (V) | Average Current (mA) | Peak Current (mA) |
---|---|---|
37V | 65 mA | 70 mA |
48V | 50 mA | 55 mA |
57V | 45 mA | 50 mA |
Installation Details
Wiring methods shall be in accordance with the National Electrical Code (ANSI/NFPA70), local codes, and the authorities having jurisdiction.
Parts List
TouchSecure®reader - 1.
Screws (A #6-18X1.5" SS ) - 2Nos - Mounting screws for Wall.
Snake Eye Screw (SMF #6-32X5/16" SS) - Top casing mounting security screw.
Screws (SMF #6-32x3/8" SS) - 3 No’s - 1 Top casing mounting screw and 2 Junction Box mounting screws.
Nylon anchor plug - 2 Nos.
6 pin phoenix plug (Phoenix connector version only) - 2 Nos.
Recommended Infrastructure
All cabling and wiring shall be UL Listed and/or UL Recognized
All readers shall be powered by UL listed PoE sourcing equipment, UL listed power-limited power supply, or power-limited output from UL listed control panel
Cable Wiegand | 22AWG Shielded cable. ( Cable P No : ALPHA WIRE, P/N 1299/10C) |
Cable RS-485 | RS-485 for 1000m** (4000ft) 24AWG STP |
Cable RJ45 | Cat5e / Cat6 |
Linear DC PS | 5 - 16V, 1A min. |
** Tested in lab conditions up to 115Kbaud
Wiring Information
Cable Color codes for Pig Tail Reader
Table 1
& Do not connect when reader is powered by Power over Ethernet.
Pin out for Phoenix Connector Reader
Table 2
Pin | Cable color | Description | Comment |
---|---|---|---|
P1.1 | Orange | LED Green |
|
P1.2 | White | Data 1 |
|
P1.3 | Green | Data 0 |
|
P1.4 | Black | Drain | Drain to be connected to cable shield |
P1.5 | Black + White | Gnd |
|
P1.6 | Red | Power | Do not connect when reader is powered by PoE |
P2.1 | Blue | Hold |
|
P2.2 | Violet | Tamper |
|
P2.3 | Gray | RS485- |
|
P2.4 | Pink | RS485+ |
|
P2.5 | Yellow | Buzzer |
|
P2.6 | Brown | LED Red |
|
During Wiring make sure that the +VDC lines does not make contact with any other cables, as it might affect reader functionality/ cause damage to the reader.
Mounting the Reader
Location of mounting holes on wall
Reader Installation Steps
Make two holes on the wall as per the image above corresponding to the type of reader.
b. Insert the nylon screw plugs into the wall.
c. Connect the wires as per the Table 1 or Table 2.
d. TouchSecure® reader with Bottom Casing is to be now secured onto the wall using the Screws (A #6-18X1.5" SS ).
e. The top casing can be inserted onto the bottom casing.
f. Secure the Top and bottom casing by the Snake Eye Screw (SMF #6-32X5/16" SS).
Power up and Testing
Turn power on
The LED blinks 3 times green with a long beep, then turns redPresent a card
The LED blinks green, and a short beep is emitted
This is the default reader behavior.
Certifications
FCC
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Re-orient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Information to user
Changes or modifications not expressly approved by Identiv could void the user's authority to operate the equipment.
IC
This Class B digital apparatus complies with Canadian ICES-003.
This device complies with Industry Canada licence-exempt RSS standard(s).
Operation is subject to the following two conditions:
(1) This device may not cause interference.
(2) This device must accept any interference, including interference that may cause undesired operation of the device.
CE
Identiv hereby declares that the TouchSecure® Model: Connectivity MUL device mentioned herein is in compliance with the essential requirements and other relevant portions of the Directive R&TTE 1999/5/EC.
UL 294
Communication via Wiegand and OSDP was evaluated by UL and serves as the interface between the reader and panel
Communication via Ethernet was not evaluated by UL.
The maximum length of the Ethernet cable when using PoE as the power source in UL installations is limited to 30 meters (98.5 feet).
UL 294 Access Control Performance Levels
Destructive attack | Level IV |
Line Security | Level I |
Endurance | Level I |
Standby Power | Level I |