Reset Encryption Flowchart

 

Resetting Encryption SNIB2 / SNIB3

 

Introduction

 

Encrypted communication between Velocity and the SNIB can be broken either because the controller was power cycled with its encryption key turned on (dipswitch 1 (S1) on switch bank 2 (SW2)), or encryption was reset in the port properties on a valid connection.

 

Below is one of the two messages in Event Viewer indicating encryption needs resetting.

Encryption Broken. Polling halted.

TLS Handshake Failed (SNIB3 Only)

 

Components of the SNIB3

Solution

Step 1: Physically set dipswitch 1 (S1) on switch bank 2 (SW2) to the ON position.

Step 2: With the switch ON, cycle power to the Controller.

Step 3: Allow the controller to fully boot. SNIB P1 LED should toggle back and forth and the system LED on the controller will flash steady green.

Step 4: In Velocity, open the port properties and check the box to reset encryption. Press OK.

 

 

 

Step 5: Set dipswitch 1 (S1) on switch bank 2 (SW2) to the OFF position to preserve encryption.

 

 

Resetting Encryption Flowchart