Table of Contents | ||
---|---|---|
|
CMD 200: CHANGE PRINTER LANGUAGE
...
A master access zone consists of up to eight standard access zones, plus tag and alert flags. In v6Version 6.6 provide provides up to four extension flags to handle SNUX conditions, two-person rules, and anti-passback options. In v7.0 these flags are moved to the user code records.
...
Several new ACBs have been added for v7. These are written in italics.
The printout created by this command is self-explanatory. Use this printout to increase your understanding of system operation. Also, it’s a good idea to print out the current ACB status before performing any ACB programming.
V6v6.6 ACBs 41-72 have been reassigned in V7v7.0. In addition, several new ACBs have been created.
...
The Action Control Block input mappings are shown below. The ACBs added for v7 are noted in red italics.
ACB | Description | Alarm Type | Trigger on Secure? 1 |
1-8 | Alarm Input 1-8 | general alarm | yes |
9-16 | Alarm Input 1-8 DOTL/AATL | general alarm | yes |
17-24 | Alarm Input 1-8 Tamper | general alarm | yes |
25-40 | Expansion Alarm Input 1-16 | general alarm | yes |
41-56 | Expansion Alarm Input 17-32 [Vn. 7.0] | general alarm | yes |
57-64 | Alarm Input 1-8 DOTL/AATL WARN [Vn. 7.0] |
| yes |
65-72 | Alarm Input 1-8 RQE/MRQ [Vn. 7.0] |
| yes |
73 | Occupancy Violation | general alarm |
|
74 | Line-Shorted | general alarm |
|
75 | Duress | duress alarm |
|
76 | Box Tamper | tamper alarm | yes |
77-92 | Kpd 1-16 Physical Tamper | tamper alarm | yes |
93-108 | Kpd 1-16 CODE Tamper | tamper alarm | yes |
109 | Tag Alert | trouble alarm |
|
110 | Line Noise | general alarm |
|
111 | Keypad Offline | trouble alarm |
|
112 | Parallel Printer Offline | trouble alarm | yes |
113 | Serial Printer Offline | trouble alarm | yes |
114 | Passback Violation | general alarm |
|
115 | UPS Fail | trouble alarm | yes |
116 | AC Fail | trouble alarm | yes |
117 | Membat Fail | trouble alarm | yes |
118 | UPS Low | trouble alarm | yes |
119 | Line Out-of-Spec | general alarm |
|
120 | Line Open | general alarm |
|
121 | Network Offline | trouble alarm | yes |
122 | Entry Delay Warning |
|
|
123 | 2-Person-Rule Violation | tamper alarm |
|
124 | Exit Delay Warning |
| yes |
125 | Modem Offline | trouble alarm | yes |
126 | Report Buffer Full | trouble alarm |
|
127 | MATCH Reader Offline | trouble alarm |
|
CODE Denial Alarms: | |||
128 | Deny: restricted address |
|
|
129 | Deny: bad CODE |
|
|
130 | Deny: restricted access zone |
|
|
131 | Deny: restricted control zone |
|
|
132 | Deny: restricted temporary days |
|
|
133 | Deny: passback violation |
|
|
134 | Deny: access CODE overridden at relay |
|
|
135 | Deny: Use Count Exceeded |
|
|
136 | Deny: Absentee Limit Count Expired |
|
|
137 | Deny: Access Override by Sgl-Zone |
|
|
138 | Deny: Paging Override |
|
|
139 | Deny: Two-Person rule incomplete |
|
|
140 | Deny: Incomplete Dual, no COTZ |
|
|
141 | Deny: Can't unmask active inputs |
|
|
142 | Deny: Day Count Exceeded |
|
|
143 | Deadman Timer Expired |
|
|
144-159 | Local Duress at reader 1-16 |
|
|
160-167 | Tagged User at Door 1-8 [Vn. 7.0] |
|
|
More CODE Denial Alarms: | |||
168-183 | Deny: Local Reader 1-16 |
|
|
184-185 | Reserved |
|
|
186 | Deny: User Disabled by Host |
|
|
187-189 | Reserved |
|
|
190 | Deny: Bad PIN (good card) |
|
|
191 | Deny: Unknown CODE, Unknown Host |
|
|
192 | Deny: Value Error |
|
|
193 | Deny: Duress |
|
|
194 | Deny: Threat Level |
|
|
195 | Deny: Reader Disabled |
|
|
196 | Deny: Code Tamper Lockout |
|
|
197 | Deny: Host timed out, no Host Grant |
|
|
198 | Deny: User Disabled by Code Tamper. |
|
|
199 | Deny: restricted access zone (Never at this reader) |
|
|
200-207 | Alarm Input 1-8 Line Fault [Vn. 7.0] |
| yes |
208-223 | Expansion Alarm Input 1-16 DOTL/AATL These were ACBs 41-56 on v6.X | alarm | yes |
224-239 | Expansion Alarm Input 17-32 DOTL/AATL | alarm | yes |
240-255 | Expansion Alarm Input 1-16 Tamper These were ACBs 57-72 on v6.X | alarm | yes |
256-271 | Expansion Alarm Input 17-32 Tamper [v7.0] | general alarm | yes |
272-303 | Expansion Alarm Input 1-32 Line Fault [v7.0] |
| yes |
304-335 | Expansion Alarm Input 1-32 DOTL/AATL WARN [v7.0] |
| yes |
336-367 | Expansion Alarm Input 1-32 RQE/MRQ [v7.0] |
| yes |
368-383 | Keypad 1 - 16 Sequential CODE Tamper Regular "Reserved" messages will also apply. | tamper alarm | yes |
384 | Reserved. |
|
|
385 | Visitor Count Short |
|
|
386 | Unescorted Visitor |
|
|
387 | Denied by Host. Regular "Denied" messages will also apply. |
|
|
388-400 | Reserved. |
|
|
...
START 270 * N * Line Module Input
(v6.6 and earlier)
START 270 * N * Line Module Input [* LMI * ... * LMI] #
(v7)
Variables:
N = Line Module Type
...