Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Table of Contents
maxLevel2

...

A master access zone consists of up to eight standard access zones, plus tag and alert flags. In v6Version 6.6 provide provides up to four extension flags to handle SNUX conditions, two-person rules, and anti-passback options. In v7.0 these flags are moved to the user code records.

...

Several new ACBs have been added for v7. These are written in italics.

The printout created by this command is self-explanatory. Use this printout to increase your understanding of system operation. Also, it’s a good idea to print out the current ACB status before performing any ACB programming.

V6v6.6 ACBs 41-72 have been reassigned in V7v7.0. In addition, several new ACBs have been created.

...

The Action Control Block input mappings are shown below. The ACBs added for v7 are noted in red italics.

ACB

Description

Alarm Type

Trigger on Secure? 1

1-8

Alarm Input 1-8

general alarm

yes

9-16

Alarm Input 1-8 DOTL/AATL

general alarm

yes

17-24

Alarm Input 1-8 Tamper

general alarm

yes

25-40

Expansion Alarm Input 1-16

general alarm

yes

41-56

Expansion Alarm Input 17-32 [Vn. 7.0]

general alarm

yes

57-64

Alarm Input 1-8 DOTL/AATL WARN [Vn. 7.0]

 

yes

65-72

Alarm Input 1-8 RQE/MRQ [Vn. 7.0]

 

yes

73

Occupancy Violation

general alarm

 

74

Line-Shorted

general alarm

 

75

Duress

duress alarm

 

76

Box Tamper

tamper alarm

yes

77-92

Kpd 1-16 Physical Tamper

tamper alarm

yes

93-108

Kpd 1-16 CODE Tamper

tamper alarm

yes

109

Tag Alert

trouble alarm

 

110

Line Noise

general alarm

 

111

Keypad Offline

trouble alarm

 

112

Parallel Printer Offline

trouble alarm

yes

113

Serial Printer Offline

trouble alarm

yes

114

Passback Violation

general alarm

 

115

UPS Fail

trouble alarm

yes

116

AC Fail

trouble alarm

yes

117

Membat Fail

trouble alarm

yes

118

UPS Low

trouble alarm

yes

119

Line Out-of-Spec

general alarm

 

120

Line Open

general alarm

 

121

Network Offline

trouble alarm

yes

122

Entry Delay Warning

 

 

123

2-Person-Rule Violation

tamper alarm

 

124

Exit Delay Warning

 

yes

125

Modem Offline

trouble alarm

yes

126

Report Buffer Full

trouble alarm

 

127

MATCH Reader Offline

trouble alarm

 

CODE Denial Alarms:

128

Deny: restricted address

 

 

129

Deny: bad CODE

 

 

130

Deny: restricted access zone

 

 

131

Deny: restricted control zone

 

 

132

Deny: restricted temporary days

 

 

133

Deny: passback violation

 

 

134

Deny: access CODE overridden at relay

 

 

135

Deny: Use Count Exceeded

 

 

136

Deny: Absentee Limit Count Expired

 

 

137

Deny: Access Override by Sgl-Zone

 

 

138

Deny: Paging Override

 

 

139

Deny: Two-Person rule incomplete

 

 

140

Deny: Incomplete Dual, no COTZ

 

 

141

Deny: Can't unmask active inputs

 

 

142

Deny: Day Count Exceeded

 

 

143

Deadman Timer Expired

 

 

144-159

Local Duress at reader 1-16

 

 

160-167

Tagged User at Door 1-8 [Vn. 7.0]

 

 

More CODE Denial Alarms:

168-183

Deny: Local Reader 1-16

 

 

184-185

Reserved

 

 

186

Deny: User Disabled by Host

 

 

187-189

Reserved

 

 

190

Deny: Bad PIN (good card)

 

 

191

Deny: Unknown CODE, Unknown Host

 

 

192

Deny: Value Error

 

 

193

Deny: Duress

 

 

194

Deny: Threat Level

 

 

195

Deny: Reader Disabled

 

 

196

Deny: Code Tamper Lockout

 

 

197

Deny: Host timed out, no Host Grant

 

 

198

Deny: User Disabled by Code Tamper.

 

 

199

Deny: restricted access zone (Never at this reader)

 

 

200-207

Alarm Input 1-8 Line Fault [Vn. 7.0]

 

yes

208-223

Expansion Alarm Input 1-16 DOTL/AATL These were ACBs 41-56 on v6.X

alarm

yes

224-239

Expansion Alarm Input 17-32 DOTL/AATL

alarm

yes

240-255

Expansion Alarm Input 1-16 Tamper These were ACBs 57-72 on v6.X

alarm

yes

256-271

Expansion Alarm Input 17-32 Tamper [v7.0]

general alarm

yes

272-303

Expansion Alarm Input 1-32 Line Fault [v7.0]

 

yes

304-335

Expansion Alarm Input 1-32 DOTL/AATL WARN [v7.0]

 

yes

336-367

Expansion Alarm Input 1-32 RQE/MRQ [v7.0]

 

yes

368-383

Keypad 1 - 16 Sequential CODE Tamper Regular "Reserved" messages will also apply.

tamper alarm

yes

384

Reserved.

 

 

385

Visitor Count Short

 

 

386

Unescorted Visitor

 

 

387

Denied by Host.

Regular "Denied" messages will also apply.

 

 

388-400

Reserved.

 

 

...

START 270 * N * Line Module Input (v6.6 and earlier)

START 270 * N * Line Module Input [* LMI * ... * LMI] # (v7)

Variables:

N = Line Module Type

...