Figure 3: Terminal Block 1
These connectors are part of Connections for Terminal Block 1 . (TB1)
...
PIN | CONNECTOR | INPUT / OUTPUT / DESTINATION |
---|---|---|
1 | 16 VAC POWER | 16V AC Power Supply (Not Used) |
2 | 16 VAC POWER | 16V AC Power Supply (Not Used) |
3 | +12 V BAT | 12V DC From Power Supply (Factory Wired) |
4 | +12 V BAT | 12V DC From Power Supply (Factory Wired) |
5 | NO | Relay 1 Normally Open |
6 | COM | Relay 1 Common |
7 | NC | Relay 1 Normally Closed |
8 | NO | Relay 2 Normally Open |
9 | COM | Relay 2 Common |
10 | NC | Relay 2 Normally Closed |
11 | D1 | Door Trip D1 N/O to Door Trip Ground (To DSM Door Switch Monitor For Relay 1 Relock on Door Open) |
12 | D2 | Door Trip D2 N/O to Door Trip Ground (To DSM Door Switch Monitor For Relay 2 Relock on Door Open) |
13 | GND | Door Trip Ground to Door Trip D1 and D2 ( To DSM Door Switch Monitor For Relock on Door Open) |
14 | B1 | Exit Button B1 N/O to Exit Button Ground (To Exit Button for Relay 1 Remote Unlock) |
15 | B2 | Exit Button B2 N/O to Exit Button Ground (To Exit Button for Relay 2 Remote Unlock) |
16 | GND | Exit Button Ground to B1 and B2 (To Exit Button Buttons for Remote Unlock) |
17 | Not Used | |
18 | GND | RS-232 communications Communications Ground to CPU (Factory Wired) |
19 | TX | RS-232 TX Communications to CPU (Factory Wired) |
20 | RX | RS-232 RX Communications to CPU (Factory Wired) |
21 | NO | Postal Lock Switch Normally Open to Control Relay 1 Unlock (Postal Lock Sold Separately) |
22 | GND | Postal Lock Switch Ground to Control Relay 1 Unlock (Postal Lock Sold Separately) |
...